Special features

  • Digital amplifier for industrial automation tasks and production process monitoring
  • 600 Hz CF measurement technology with TEDS sensor detection for SG full bridges
  • Fast peak and limit value monitoring and digital inputs/outputs
  • Accuracy class, typically 0.05%
  • Modular mounting on a DIN EN 60715 type DIN rail (IEC 60715)
  • Standardized CANopen CiA fieldbus coupling for parameterization and backup

digiCLIP

Accuracy class (at UB = 2.5 V and UB = 1 V); after autocalibration

0.05 type.

1.1 in an industrial environment as per EN 61326

1.2 in the 10 mV/V measuring range

Power supply

Supply voltage,

Overvoltage and reverse polarity protection

VDC

24

Isolation voltage

Potential separation between the supply bus and transducer connection, functional separation, must not be considered for safety aspects

VDC

500

Permissible supply voltage range

V

18 ... 30

Influence of supply voltage when there are changes in the specified range

%/V

< 0.001

Power consumption, max.; incl. transducer

W

2.0

Amplifier

Carrier frequency, rectangle

Hz

600 (591.9 Hz ±100 ppm)

Synchronization

when several interconnected modules are used, the carrier frequency is synchronized automatically

Bridge excitation voltage UB,

Peak−to−peak (±10%)

V

2.5

1.0

Measuring range

mV/V

±4

±10

Connectable transducers

SG full bridge

ohms

80 ... 5000

Connection technique

4 and 6−wire circuitry with single-wire open-circuit monitoring

Permissible cable length between transducer and amplifier, max.

m

100

Input resistance

MOhm

>5

Measurement frequency range, adjustable (−3dB) (see filter table)

Hz

0.05 ... 225

Filter characteristics

Bessel, 4th order

Noise voltage relative to input, for UB = 2.5 V, typical

µV/V

1.0 (at filter frequenzy 100 Hz)

0.05 (at filter frequenzy 1 Hz)

Influence of ambient temperature for change of 10 K

on the zero point (TK0) on sensitivity (TKC)

µV/V

%

0.1

0,05 f.s.

Linearity deviation

% f.s.

0.005

Long−term drift, without AutoCal

%

<0.001 (within 48 h)

Communication interface

Number of devices on the bus, max. Address settings

Protocol Hardware bus link Bit Rate

Line length, max. Bit rate selection PDO transfer

Cycle time for time-driven triggering, Possibly restricted by chosen data types and

filter frequency 1)

CAN connection

kBits/s m

ms

99

1 to 99 via rotary switch on front

CAN 2.0B, CANopen-compatible, CiA DS301, DS404 Two-wire, as per ISO 11898; available at www.can−cia.org 1000 500 250 125 100 50

25 100 250 500 600 1000

Automatic detection after change of address Triggered by sampling rate, timing control or SYNC message

0.85 ... 25000

Side connector terminal; electrically isolated from supply and measurement ground Option: DF002: 9−pin Sub-D (CAN−CiADR303−1)

Signal conditioning

A/D converter

Delta-Sigma, 24−bit

Scaling accuracy

bits

32

Sampling rate

1/s

1184